What is the relationship between the length of a wire, its AWG, and its amperage rating?

A wire that will carry 15A without overheating, will carry 15A whether it is 1 meter long, or 1 km long. What will change is the resistance, and resistance is directly related to voltage drop.

If you are powering a 120V load that draws, say 10A., if your wire has a resistance of 0.100\$\Omega\$ (half that in each direction), then there will be a voltage drop of 0.100\$\Omega\$ * 10A = 1V. Your load will not actually see a 120V supply, but a 120-1=119V supply.

Now, if your wire were the same gauge, but 10 times as long, there would be a voltage drop of 10V. Your load would see a 110V supply. Longer still, and you get the idea.

You may wonder what happens if the wire is 120 times as long. Will there be a voltage drop of 120V, and no voltage appearing at the load?

Only if the load acts like a short circuit when there is no voltage applied to it.

As the voltage on the load changes, the current through the load and the wire will probably also change. Some loads are resistive, like incandescent light bulbs. As the voltage across them drops, the current through them will also drop. Other loads behave differently. Some loads will attempt to compensate for a low supply voltage by drawing more current. An example would be most PCs. In such a case, a longer power cord, could cause the PC to draw more current. (Thanks to Bruce Abbott and JonRB for drawing attention to that phenomenon.)

I suppose in a worst case scenario, the current drawn by a load with a very long power cord could be above that for which the cord is rated. However, this would only happen if a fuse or circuit breaker is not present which is properly rated for the current carrying capacity of the wire.

To counteract the voltage drop of long wires, you can use a thicker gauge. That will decrease the resistance and voltage drop. But that is a separate issue from the ampacity or current carrying capacity of the wire. The current carrying capacity of a wire does not change with its length.


Yes. The longer the distance, the lower the the gauge (larger diameter), to maintain the service voltage at the point of load. If you are following electrical code guidelines, 3% is the magic number.

The National Electrical Code (NEC) recommends a maximum voltage drop of 3 percent for individual household circuits (known as branch circuits).

enter image description here

Or use this voltage drop calculator:

enter image description here

Note the maximum current is set to 15A in this calculation, but for continuous loads it should be derated to 50%, and for unknown loads the budget should not exceed 80%. Both these cases will give you longer maximum lengths.

https://www.calculator.net/voltage-drop-calculator.html?material=copper&wiresize=8.286&voltage=120&phase=ac&noofconductor=1&distance=50&distanceunit=feet&amperes=15&x=55&y=23

https://www.thespruce.com/wire-size-underground-circuit-cable-length-1152899


There is a lot to this question.

The first concept is ampacity. This is a thermal limit based on assumptions. In order to avoid having the wire get too hot for the insulation, you have to use a wire with the proper ampacity. Length doesn't matter. Insulation temperature rating of the insulation does matter. Also the details of how the wire is routed (in conduit or behind insulation, etc) matter.

https://www.cerrowire.com/products/resources/tables-calculators/ampacity-charts/

You should never use wire above its ampacity rating unless you know what you are doing. The melting point of copper is pretty high. So you may be able to run a lot of current through bare copper wire, or wire with high temperature insulation. I don't think there are tables for that. You have to do your own calculations or test and verify.

The second concern is voltage drop. This only depends on wire cross-section area and length. Longer length means more resistance and more voltage drop. small cross section also means more resistance and more voltage drop.

There are tables for this too. You can also calculate it if you know the resistance (Ohms per foot or Ohms per meter).

https://www.cerrowire.com/products/resources/tables-calculators/voltage-drop-tables/

One more thing. The resistance of copper (and almost all metals) increases with temperature. The increase is about 4 percent every 10 degrees C for copper. So if you ever do run copper hot, keep that in mind.